Climate zones run from 1 (hot, such as southern Florida and Hawaii) to 8 (subarctic Alaska). Look up yours on the DOE or ENERGY STAR climate zone map.
How the R-value calculator works
RValueCalc multiplies the depth of the existing insulation by its typical R-value per inch, subtracts that from your target and divides the rest by the new material's R-value per inch. The range uses the lowest and highest per-inch values in the chart. U = 1 ÷ R, RSI = R × 0.1761 and heat flow = area × temperature difference ÷ R.
R-value per inch
| Material | R per inch | Typical | Inches for R-30 | Inches for R-49 |
|---|---|---|---|---|
| Fiberglass batt | 2.9–3.8 | 3.2 | 9.4 | 15.3 |
| Loose-fill fiberglass | 2.2–2.7 | 2.5 | 12 | 19.6 |
| Loose-fill cellulose | 3.2–3.8 | 3.5 | 8.6 | 14 |
| Mineral wool batt | 3–4.3 | 4 | 7.5 | 12.3 |
| Loose-fill mineral wool | 2.8–3.3 | 3 | 10 | 16.3 |
| Open-cell spray foam | 3.5–3.7 | 3.6 | 8.3 | 13.6 |
| Closed-cell spray foam | 6–7 | 6.5 | 4.6 | 7.5 |
| EPS foam board | 3.6–4.4 | 4 | 7.5 | 12.3 |
| XPS foam board | 4.6–5 | 5 | 6 | 9.8 |
| Polyiso foam board | 5.6–6.5 | 6 | 5 | 8.2 |
ENERGY STAR recommended R-values (existing wood-framed homes)
| Zone | Attic, uninsulated | Attic with 3–4″ already | Floor |
|---|---|---|---|
| Zone 1 | R-30 | add R-25 | R-13 |
| Zone 2 | R-49 | add R-38 | R-13 |
| Zone 3 | R-49 | add R-38 | R-19 |
| Zones 4A and 4B | R-60 | add R-49 | R-19 |
| Zones 4C, 5 and 6 | R-60 | add R-49 | R-30 |
| Zones 7 and 8 | R-60 | add R-49 | R-38 |
Per-inch values: US Department of Energy and Building America Solution Center (PNNL) typical ranges; mineral wool batts vary most (older batts ≈ R-3.1, current stone-wool batts up to ≈ R-4.3). Recommended levels: ENERGY STAR, based on 2021 IECC Table R402.1.3. Results are estimates: product labels give the rated R-value for a stated thickness, and local codes set the legal minimums.
Frequently asked questions
What R-value for floors?
R-13 in zones 1–2, R-19 in zones 3–4B, R-30 in zones 4C–6 and R-38 in zones 7–8 (ENERGY STAR).
What about walls?
When siding is replaced, blow insulation into empty cavities and add insulating sheathing: R-5 in zone 3, R-5 to R-10 in zones 4–8.
Are these building code minimums?
They are ENERGY STAR retrofit recommendations based on the 2021 IECC. New construction must meet the code adopted where you live.
Is RValueCalc free?
Yes, with no sign-up or ads.
Are my inputs saved?
Yes, in this browser only.